6. Special Function
The series UPS has some special functions, which could satisfy some
special application of user. And the functions have own features,
please contact your local distributor for further information before
using the function.
6.1 HE Function
6.1.1 Brief Introduction of HE Function
If HE function is set to enable, after the UPS is turned on, the power
used by the load is directly supplied from the utility power via internal
filter while the utility power is in normal range, so the high efficiency
could be gained in HE mode. It is also called economy mode. Once the
mains is loss or abnormal, the UPS would transfer to Line mode or
Battery mode and the load is supplied continuously.
The great virtue is overall high efficiency >0.97 of UPS, to save power
for user.
But the disadvantage is 1) the load can not be protected as well as in
Line mode, for the load is directly supplied from the utility; 2) the
transfer time of UPS output from HE mode to Battery mode is about
10ms.
So the function is not suitable to some sensitive loads, and the region
where the utility power is unstable.
6.2 Converter Function
6.2.1 Brief introduction of Converter function
In converter mode, the UPS would free run with fixed output
frequency (50Hz or 60Hz). Once the mains is loss or abnormal, the
UPS would transfer to Battery mode and the load is supplied
continuously.